Offshore · L2 maintenance · April 2026

L2 maintenance on an ABB 37 MVA generator aboard an FPSO

Offshore operation aboard an FPSO · Mexico · April 2026

Project summary

What the service covered

An ABB AMS 1250 LE generator rated at 37 MVA, 11 kV and 1,800 rpm received L2 maintenance in a marine environment. The service assessed the main windings, excitation system, PMG and rectifier diodes.

The April 2026 report documented satisfactory electrical results and recommended continued monitoring. External corrosion remained a finding requiring specific attention.

37 MVA

Nameplate rating

ABB AMS 1250 LE · 11 kV

L2

Completed scope

Onboard maintenance · April 2026

Satisfactory

Electrical result

Reported condition at completion; continue monitoring

Unresolved

External corrosion

Requires attention and a specific scope

Define a feasible onboard scope

Access and available space constrain handling of an offshore generator. The preliminary survey identified that rotor removal was not feasible at the existing location without first resolving the lifting plan and required equipment.

  • 37 MVA synchronous generator in a marine environment
  • Moisture as a relevant condition when interpreting tests
  • Clearance and handling arrangements to verify before major disassembly

Equipment serviced

Offshore synchronous generator

OEM
ABB
Model
AMS 1250 LE
Rating
37,000 kVA
Voltage
11 kV
Speed
1,800 rpm

L2 maintenance and electrical assessment

The intervention included inspection of accessible areas and testing of electrical components. Interpretation of the results considered the site's environmental conditions.

Completed activities

  • Internal visual inspection of windings, connections and accessible areas
  • Insulation-resistance and winding-resistance measurements
  • Step-voltage, surge and partial-discharge assessment as documented in the report
  • PMG, excitation-system and rectifier-diode checks
  • Recording of external corrosion and follow-up recommendations

Technical reference

Technical report TMS-SE-RE-10

Findings and follow-up

Electrical results were within the report's assessment criteria. Some polarization and absorption indices were slightly low; the report linked them mainly to moisture in the marine environment.

Internal inspection did not record excessive contamination, oil leaks or significant visible damage in accessible areas. Externally, corrosion was identified on covers, guards, the structure and fasteners.

The preliminary survey and L2 maintenance are different scopes. The documented service did not include rotor removal or an L3/L4 overhaul. A major intervention requires prior resolution of space, lifting and onboard logistics.

The results describe the condition observed in April 2026. Scheduling the next service should consider current measurements, corrosion progression and the client's operating window.

Questions about this service

Did the service include rotor removal?

No. L2 maintenance was performed. The preliminary survey identified space and handling restrictions that must be resolved before proposing removal.

Was the external corrosion resolved?

The completion report records external corrosion as a finding still requiring attention. Treatment needs a specific scope and an assessment of the current condition.

What information is needed to assess another offshore generator?

Manufacturer, model, rating, location, symptoms and outage window. Major handling operations also require review of access, space and available lifting equipment.

Documentary traceability

Assessment against the service report

Technical report TMS-SE-RE-10 · April 2026

The client is described by sector to protect commercial information. Equipment data and service results remain tied to the original TEMISA service record. The findings describe the documented intervention, not the generator's current condition.