EL CID test on the generator stator core

EL CID magnetizes the stator core at 4% of normal flux and a sensor measures fault current slot by slot to find shorted laminations.

Published · 41.1 seconds · subtítulos en español

Email ventas@temisapowergen.mxWhatsApp

Short answer

What is the EL CID test on a generator core?

A low-flux test that finds shorts between stator core laminations without running the generator. EL CID magnetizes the core with only 4% of normal flux and a sensor scans every slot measuring fault current. The reading must be interpreted, and if in doubt it is confirmed with a rated flux test.

Video transcript

Download captions (.srt)
  1. 00:00

    How do you find a

  2. 00:01

    hidden short in a generator

  3. 00:02

    core without energizing it?

  4. 00:04

    It's not running it,

  5. 00:05

    it's a low flux test.

  6. 00:07

    The stator core is thousands

  7. 00:08

    of laminations insulated from each

  8. 00:10

    other;

  9. 00:11

    if two touch,

  10. 00:12

    a hot spot forms that

  11. 00:13

    can burn the coils.

  12. 00:14

    Like finding a leak with

  13. 00:15

    just a trickle:

  14. 00:16

    you don't need to open

  15. 00:17

    the tap all the way.

  16. 00:18

    The EL CID test magnetizes

  17. 00:20

    the core with only 4%

  18. 00:22

    of normal flux,

  19. 00:23

    and a sensor scans every

  20. 00:24

    slot measuring fault current.

  21. 00:26

    But careful,

  22. 00:27

    the reading has to be

  23. 00:28

    interpreted well,

  24. 00:28

    and if in doubt it's

  25. 00:30

    confirmed with a rated flux

  26. 00:31

    test.

  27. 00:32

    So it's not running to

  28. 00:33

    see,

  29. 00:34

    it's measuring to know.

  30. 00:35

    Has yours had an EL

  31. 00:36

    CID?

  32. 00:37

    Comment CORE and we'll tell

  33. 00:38

    you what to check.

Questions from plant owners

What is EL CID used for?

To find shorts between stator core laminations, which form hot spots that can damage coil insulation.

Why only 4% of normal flux?

Low flux is enough to measure fault current between shorted laminations without a large power supply.

What if the reading is unclear?

It is interpreted against history and the manufacturer's criteria and, if in doubt, confirmed with a rated flux test.

Does TEMISA Power Gen perform EL CID?

Yes, on site or at the Tlajomulco shop. Contact ventas@temisapowergen.mx.

About the figures: Figures and graphics in the video illustrate the phenomenon. They are not a measurement from a serviced generator and they are not acceptance limits.

About the footage: The video is a TEMISA Power Gen explainer animation. It does not document a customer's machine.

Technical sources

These references identify equipment families or background documents. They are not an endorsement by the publisher and they are not an assessment of your generator.

Narration of the TEMISA Power Gen explainer video.