Generator end-winding bump test: 120 Hz resonance

End windings are pushed at twice line frequency, 120 Hz. If their natural frequency is close, they resonate. The bump test measures it.

Published · 41.4 seconds · subtítulos en español

Email ventas@temisapowergen.mxWhatsApp

Short answer

What is an end-winding bump test on a generator?

An impact test with an instrumented hammer that measures the natural frequencies of the stator end windings. Outside the core they hang free, tied with supports and wedges, and magnetic forces push them at twice line frequency, 120 Hz on a 60 Hz grid. If a natural frequency falls near 120 Hz they resonate, ties loosen and insulation wears. Those frequencies change over the years, so the test is repeated.

Video transcript

Download captions (.srt)
  1. 00:00

    Why do a generator's end

  2. 00:01

    windings get pushed 120 times

  3. 00:03

    per second?

  4. 00:04

    It's not machine vibration,

  5. 00:06

    it's magnetic force.

  6. 00:08

    Outside the core they hang

  7. 00:09

    free,

  8. 00:09

    tied with supports and wedges,

  9. 00:11

    and the current pulls them

  10. 00:13

    at twice the grid frequency.

  11. 00:15

    Like the glass that shatters

  12. 00:16

    with one exact note:

  13. 00:17

    it's not the force,

  14. 00:19

    it's the frequency.

  15. 00:20

    If their natural frequency falls

  16. 00:21

    near 120 Hz,

  17. 00:23

    they resonate,

  18. 00:24

    the ties loosen and the

  19. 00:25

    insulation wears.

  20. 00:27

    But careful,

  21. 00:28

    those frequencies change over the

  22. 00:29

    years.

  23. 00:29

    That's why a bump test

  24. 00:31

    is done with an instrumented

  25. 00:32

    hammer.

  26. 00:33

    So it's not noise,

  27. 00:34

    it's resonance.

  28. 00:36

    Has yours had a bump

  29. 00:36

    test?

  30. 00:37

    Comment RESONANCE and we'll tell

  31. 00:39

    you what to check.

Questions from plant owners

Why do end windings vibrate at 120 Hz?

Magnetic force depends on current squared, so it pulses at twice line frequency: 120 Hz on a 60 Hz grid.

What if the natural frequency is near 120 Hz?

They resonate: small force, large motion. Ties, supports and wedges loosen and the insulation wears.

How is a bump test done?

With the machine offline, the end winding is struck with an instrumented hammer and the response measured with accelerometers.

Does TEMISA Power Gen do it on site?

Yes, on site or at the Tlajomulco shop. Contact ventas@temisapowergen.mx.

About the figures: Figures and graphics in the video illustrate the phenomenon. They are not a measurement from a serviced generator and they are not acceptance limits.

About the footage: The video is a TEMISA Power Gen explainer animation. It does not document a customer's machine.

Technical sources

These references identify equipment families or background documents. They are not an endorsement by the publisher and they are not an assessment of your generator.

Narration of the TEMISA Power Gen explainer video.