Generator synchronizing: the damage of closing out of phase

Closing out of phase hits the shaft, couplings and windings. IEEE allows up to 10 degrees of angle with tight frequency and voltage limits.

Published · 45.6 seconds · subtítulos en español

Email ventas@temisapowergen.mxWhatsApp

Short answer

How can synchronizing damage a generator?

When the breaker closes, generator and grid must be in step: same voltage, frequency and angle. Out of phase, the grid yanks the rotor in one jolt and hits the shaft, couplings and windings. IEEE allows closing with up to 10 degrees of angle difference, with tight frequency and voltage limits; outside them the standard no longer guarantees the generator comes out undamaged.

Video transcript

Download captions (.srt)
  1. 00:00

    How can a power plant

  2. 00:01

    generator get damaged with no

  3. 00:02

    fault at all?

  4. 00:04

    It's not a short,

  5. 00:05

    it's synchronizing.

  6. 00:06

    When the breaker closes,

  7. 00:08

    generator and grid must be

  8. 00:09

    in step:

  9. 00:10

    same voltage,

  10. 00:11

    same frequency and same angle.

  11. 00:13

    Like stepping onto an escalator:

  12. 00:15

    step off-beat and the stair

  13. 00:17

    yanks you.

  14. 00:18

    Out of phase,

  15. 00:19

    the grid yanks the rotor

  16. 00:20

    in one jolt and hits

  17. 00:21

    the shaft,

  18. 00:22

    couplings and windings.

  19. 00:25

    IEEE allows closing with up

  20. 00:26

    to 10 degrees of angle

  21. 00:27

    difference,

  22. 00:28

    with very tight frequency and

  23. 00:29

    voltage limits.

  24. 00:31

    But careful,

  25. 00:31

    outside those limits the standard

  26. 00:33

    no longer guarantees it comes

  27. 00:34

    out undamaged.

  28. 00:36

    So it's not a fault,

  29. 00:38

    it's a bad match.

  30. 00:39

    Has yours jolted when synchronizing?

  31. 00:41

    Comment SYNC and we'll tell

  32. 00:43

    you what to check.

Questions from plant owners

What must match to synchronize a generator?

Voltage, frequency and phase angle of the generator and the grid when the breaker closes.

What happens if the breaker closes out of phase?

The grid yanks the rotor in one jolt, hitting the shaft, couplings and windings, even with no electrical fault.

How much angle difference does the standard allow?

The video cites IEEE: up to 10 degrees, with very tight frequency and voltage limits. Outside them the standard no longer guarantees an undamaged generator.

What is checked after a bad synchronization?

A generator assessment: stator windings, end-winding bracing, rotor and couplings. Contact ventas@temisapowergen.mx.

About the figures: Figures and graphics in the video illustrate the phenomenon. They are not a measurement from a serviced generator and they are not acceptance limits.

About the footage: The video is a TEMISA Power Gen explainer animation. It does not document a customer's machine.

Technical sources

These references identify equipment families or background documents. They are not an endorsement by the publisher and they are not an assessment of your generator.

Narration of the TEMISA Power Gen explainer video.