TEMISA Power Gen · Explainer
Ver en españolNegative sequence: how a grid fault heats the rotor
Unbalanced current creates a negative sequence field that heats the rotor surface, wedges and rings. Directly cooled cylindrical rotors are limited to 10.
Published · 41.3 seconds · subtítulos en español
Short answer
How does negative sequence current damage the rotor?
When the phases aren't even, negative sequence appears: a field spinning backward at double frequency against the rotor. It quickly heats the rotor surface, wedges and rings. On directly cooled cylindrical rotors the standard limits the I2²t constant to 10. If negative sequence protection is set wrong, the damage goes unnoticed.
Video transcript
Download captions (.srt)- 00:00
How can a distant fault
- 00:01
on the grid damage your
- 00:02
generator's rotor?
- 00:03
It's not a generator fault,
- 00:05
it's unbalanced current.
- 00:07
When the phases aren't even,
- 00:08
negative sequence appears:
- 00:10
a field spinning backward,
- 00:11
at double frequency,
- 00:12
against the rotor.
- 00:14
Like swimming against the current
- 00:15
at double speed:
- 00:16
all that effort turns into
- 00:18
heat.
- 00:18
That field quickly heats the
- 00:20
rotor surface,
- 00:21
the wedges and the rings.
- 00:23
On cylindrical rotors with direct
- 00:24
cooling,
- 00:25
the standard limits that constant
- 00:26
to 10.
- 00:27
But careful,
- 00:28
if the negative sequence protection
- 00:29
is set wrong,
- 00:30
the damage goes unnoticed.
- 00:32
So it's not the fault
- 00:33
outside,
- 00:34
it's what it leaves inside.
- 00:36
Have you checked your protection?
- 00:37
Comment SEQUENCE and we'll tell
- 00:38
you what to check.
Questions from plant owners
What is negative sequence?
The unbalanced-current component that creates a field spinning backward, at double frequency, against the rotor.
Which rotor parts get damaged?
The rotor surface, wedges and retaining rings heat up very quickly.
What limit does the standard give?
For directly cooled cylindrical rotors the video cites a limit of 10 for I2²t.
What should be checked?
The negative sequence protection settings and, after an event, the rotor condition. Contact ventas@temisapowergen.mx.
About the figures: Figures and graphics in the video illustrate the phenomenon. They are not a measurement from a serviced generator and they are not acceptance limits.
About the footage: The video is a TEMISA Power Gen explainer animation. It does not document a customer's machine.
Technical sources
- IEEE C50.13-2014 · Cylindrical-rotor synchronous generators — Sets negative sequence (I2²t) capability for cylindrical-rotor generators.
These references identify equipment families or background documents. They are not an endorsement by the publisher and they are not an assessment of your generator.
Narration of the TEMISA Power Gen explainer video.